High frequency dual conversion online design; Modular design;
Mainly used in scenarios such as data centers and computing sites;
Provide stable and pure AC power supply for customer loads.
Excellent load adaptability; High input power factor;
Dual conversion pure online architecture, zero conversion time for battery mains power supply mode switching, supporting fixed frequency output, effectively ensuring load power supply reliability
Adopting advanced DSP digital control technology to provide stable and reliable sine wave power supply
90V~300V wide input voltage and 40~70Hz frequency input range, compatible with harsh power environments, reducing battery discharge times and improving battery life
| communication input | |
|---|---|
| wiring method | L/N PE |
| rated voltage | 208/220/230/240Vac |
| voltage range | 90~300VAC |
| frequency range | 40Hz-70Hz |
| Input power factor | ≥0.99 |
| communication output | |
|---|---|
| wiring method | L/N PE |
| output voltage | 208/220/230/240Vac |
| Voltage regulation rate | ±1% |
| output frequency | 50/60 ± 4Hz (synchronous mode)/50/60Hz ± 0.1 (free running) |
| waveform | pure sine wave |
| Distortion (THDV%) | Linear load<2%> |
| overload capacity | 105%~125% rated load: 10 minutes/126%~150% rated load: 30 seconds/>150% rated load: 0.2 seconds |
| Convert time | Battery<>mains mode: 0 milliseconds |
| battery input | |
|---|---|
| Rated battery voltage | 192VDC or 240VDC external connection |
| battery capacity | External battery (capacity/configuration), depending on the situation |
| Backup time | External battery (capacity/configuration), depending on the situation |
| charging current | 4A |
| physical properties | |
|---|---|
| Case type | Rack/tower convertible |
| size | Uninterruptible power supply: 440mm (width) x 88mm (2U) (height) x 521mm (depth) Battery pack: 440mm (width) x 132mm (3U) (height) x 525mm (depth) |
| weight | Uninterruptible power supply: 10.8kg/12.6kg Battery pack: 40.8kg (16 cells * 1 pack * 7AH/12V)/61.3kg (20 cells * 1 pack * 7AH/12V) |
| human-machine interface | |
|---|---|
| LCD display | Display input mains voltage, frequency, load level, operating mode, and equipment health status |
| Standard communication port | 1. RS232 2. USB port 3 Emergency shutdown/remote power on/off interface (EPO/COO) 4. Smart card slot |
| Optional expansion card | MODBUS, RS485, SNMP, AS400 expansion card |
| Durability of operating environment | |
|---|---|
| temperature range | -10~40℃ |
| relative humidity | 0-97% (no condensation) |
| noise | <55db>at a distance of 1 meter |