 (1).png)
High frequency dual conversion online design; Modular design;
Mainly used in scenarios such as data centers and computing sites;
Provide stable and pure AC power supply for customer loads.
Excellent load adaptability; High input power factor;
| Model |
3C10K |
3C10KS |
3C15K |
3C15KS |
3C20K |
3C20KS |
||||||
| rated power |
VA/W |
10kVA/9kW |
15kVA/13.5kW |
20kVA/18kW |
||||||||
| Machine Architecture |
Dual conversion onlineUPS |
|||||||||||
| Input/output phase number |
Three phase input/Single phase output |
|||||||||||
| input |
Number of input lines |
Single phase two wire(L,N)protected area or three-phase four-wire(L1,L2,L3,N)protected area |
||||||||||
| Input voltage range |
Single phase zero fire phase voltage: 90~300VAC / Three phase line voltage: 150~500VAC |
|||||||||||
| Input frequency range |
40Hz-70Hz |
|||||||||||
| Input power factor |
>0.99Single phase mode ≥0.9 Three phase mode |
|||||||||||
| output |
Number of output lines |
Single phase two wire(L,N)protected area |
||||||||||
| rated voltage |
208/220/230/240VAC |
|||||||||||
| Output voltage accuracy |
±1% |
|||||||||||
| output frequency |
50/60±4Hz(Lock in mode) 50/60Hz±0.1%(Fixed frequency mode) |
|||||||||||
| output waveform |
pure sine wave |
|||||||||||
| Output distortion degree (THDV%) |
<2%(linear load) |
|||||||||||
| <8%(Nonlinear load) |
||||||||||||
| overload capacity |
Commercial power mode,Battery mode(240VDC): 10minute@105%~125%rated load 60second@126%~150%rated load 0.2second@>150%rated load |
|||||||||||
| Battery mode(192VDC) : 60second@102%~125%rated load 0.2second@>125%rated load |
||||||||||||
| efficiency |
Mains mode |
94% |
||||||||||
| battery mode |
192VDC:92% / 240VDC:93% |
|||||||||||
| battery and charger |
battery voltage/quantity |
192VDC 16section (internal) |
192/240VDC 16/20section (external) |
192VDC 32section (internal) |
192/240VDC 16/20section (external) |
192VDC 32section (internal) |
192/240VDC 16/20section (external) |
|||||
| battery capacity |
12V/7AH |
External battery determines |
12V/7AH |
External battery determines External battery determines |
12V/9AH |
External battery determines |
||||||
| Backup time |
>6minute @half a year |
>4minute @half a year |
>2minute @half a year |
|||||||||
| charging current |
marking machine(Built in battery):2A Long lasting machine(External battery):4A |
|||||||||||
| human-machine interface |
LCDdisplay screen |
Display input and output voltage, frequency, load percentage, operating mode, machine status |
||||||||||
| communication interface |
standard configurationRS232, USB,Smart card slot, EPO/ROO |
|||||||||||
| Optional accessories |
No battery start module,SNMPCard, dry connection point card,MODBUSDust proof net |
|||||||||||
| standard |
EMCstandard |
IEC/EN 62040-2/ GB 7260.2 |
||||||||||
| National Standard |
GB/T 7260.1 |
|||||||||||
| industry standard |
YD/T 1095-2008 / CQC3108-2011/YD 5083-2005 |
|||||||||||
| environmental parameters |
Working temperature range |
-10~45oC |
||||||||||
| Working humidity range |
0-98%(non-condensing) |
|||||||||||
| noise |
<60dB @ 1 meters |
|||||||||||
| Protection level |
IP20 |
|||||||||||
| Applicable to polluted environments |
pollution level 2 |
|||||||||||
| Use overvoltage level |
overvoltage level Ⅱ |
|||||||||||
| altitude |
≤2000mNo reduction, maximum5000m |
|||||||||||
| Physical appearance |
size |
3C10KS:190(Width)x 340(High)x 562(Deep) 3C10K:190(Width)x 472(High)x 588(Deep) 3C10KRS:3U 440(Wide)x132(High)x 526(Deep) 3C15KS/3C20KS:239(Width)x 529(High)x 581(Deep) 3C15K/3C20K:299(Width)x 702(High)x 773(Deep) 3C15KRS/3C20KRS:4U 440(Wide)x 176(High)x 568(Deep) |
||||||||||